Exemplum |
YW-HQ3110G(L) |
YW-H HQ3115G(L) |
YW-H HQ3120G(L) |
|||
Capacitas |
10KVA |
15KVA |
20KVA |
|||
Input |
||||||
Voltage aestimatum |
380Vac (Tres - phasium + N) |
|||||
Ambitus voltage |
190 Vac~520 Vac @50% oneris; 305 Vac~478Vac @100% oneris |
|||||
Frequens Ambitus |
46Hz - 54 Hz @50Hz systemate; 56Hz - 64 Hz @60Hz systemate |
|||||
Factor Potentiae |
≥0.99@100% onus |
|||||
Output |
||||||
Output Voltage |
208/220/230/240VAC |
|||||
Exactio Voltaminis |
± 1% |
|||||
Frequentia Campus (Synchronus Campus) |
46Hz - 54 Hz aut 56Hz - 64 Hz |
|||||
Campus Frequentiae (Modus Bateriae) |
50 Hz ± 0.1Hz aut 60 Hz ± 0.1Hz |
|||||
Factor Potentiae |
Typicum 0.8 (Optionale 0.9) |
|||||
Ratio Currentis Maxima |
3:1 |
|||||
Capacitas Supra oneri (Modus Utilitatis) |
105% - 110%: 10 minuta; 110% - 130%: 1 minuta; >130%: 1 secunda |
|||||
Capacitas Supra oneri (Modus Accumulatoris) |
105% - 110%: 30 secundae; 110% - 130%: 10 secundae; >130%: 1 secunda |
|||||
Totalis corruptelam harmonicam (THD) |
≤2% @ 100% onere lineari; ≤5% @ 100% onere non lineari |
|||||
Tempus Transferendi |
||||||
Utilitas → Bateria |
0 ms |
|||||
Inversor → Bypass |
0 ms |
|||||
Efficientia |
||||||
Modus Inversoris |
>93% |
>92% |
||||
Batteria (Unitas normativa) |
||||||
Numerus Pilearum |
Praeordinata 16 sectiones (Regulabilis a 16 ad 20 sectiones) |
Praeordinatus 2 x 16 sectiones (Regulabilis a 16 - 20 sectionibus) |
||||
Tempus incarandi batteriae |
9 horas ad 90% capacitatis assequendam |
|||||
Currentis Incharging |
1A |
2A |
||||
Dato voltage |
218.4Vdc ± 1% |
|||||
Caracteres Physici |
||||||
Dimensio Profunditas × Latitudo × Altitudo (mm) |
592 x 250 x 576 |
815 x 250 x 826 |
||||
Net Pondus (kg) |
83 |
164 |
||||
Environmental Conditions |
||||||
Ambiens Operativum |
Humiditas relativa 0 - 95% et temperatura 0 - 40°C (non - condensans) |
|||||
Gradus strepitus |
< 60 dB(A) @ 1m |
|||||
Management |
||||||
Intelligent RS - 232 vel USB |
Compatibilis cum Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, et MAC |
|||||
SNMP facultativum |
Potes gestionem energiae a gestore SNMP et perambulatori web |
|||||