Product Model |
C6K Rack |
C6KS Rack |
C10K Rack |
C10KS Rack |
||||
Rated Output Capacity |
6000VA/5400W |
6000VA/5400W |
10000VA/9000W |
10000VA/9000W |
||||
Output Characteristics |
||||||||
Output Waveform |
Sine Wave |
|||||||
Rated Voltage |
208/220/230/240VAC |
|||||||
Output Voltage Accuracy |
±1% |
|||||||
Output Voltage Total Harmonic Distortion |
<1% for linear load, <4% for non-linear load |
|||||||
Output Frequency (Battery Mode) |
(50/60±0.1)Hz |
|||||||
Operating Efficiency |
95%; Efficiency in ECO mode ≥98% |
|||||||
Overload Capacity |
125% for 10 minutes; 150% for 1 minute |
|||||||
Input Characteristics |
||||||||
Input Voltage Range |
110VAC - 276VAC |
|||||||
Input Frequency Range |
40 - 70Hz |
|||||||
Input Connection |
Single - phase three - wire (live wire/neutral wire/ground wire) |
|||||||
Input Harmonic Current |
<3% |
|||||||
Input Power Factor |
≥0.99 |
|||||||
Battery Configuration and Management |
||||||||
Configurable Number of 12V Batteries |
Default 16 pieces, long-machine 16 - 20 pieces can be set |
|||||||
Battery Backup Time (75% Load) |
6.5 minutes |
- |
5 minutes |
- |
||||
Charging Capacity |
Default 1.4A, 1 - 4A can be set |
Default 4A, 1 - 12A can be set |
Default 2A, 1 - 4A can be set |
Default 4A, 1 - 12A can be set |
||||
Interfaces and Communication Management |
||||||||
Operation and Display Panel |
LCD + LED |
|||||||
Standard Communication Interface |
RS232/USB |
|||||||
Communication Slot |
1 piece, standard configuration |
|||||||
Expandable Communication Cards |
NMC card, CMC card, AS400 card, SPCC card |
|||||||
Emergency Power Off (EPO) Interface |
Standard configuration |
|||||||
Programmable Dry-contact Interface |
1 input + 1 output, standard configuration |
|||||||
Communication Software |
Winpower |
|||||||
Physical Parameters |
||||||||
Main Unit Dimensions WDH (mm) |
438*571*86.3 |
|||||||
Main Unit Installation Height |
2U |
|||||||
Main Unit Weight (Kg) |
13.3 |
13.6 |
15.2 |
15.5 |
||||
Battery Module Dimensions WDH (mm) |
438*594*130 |
|||||||
Battery Module Installation Height |
3U |
|||||||
Battery Module Weight (Kg) |
46 |
- |
52 |
- |
||||
Main Unit Shipping Dimensions WDH (mm) |
586*766*238 |
|||||||
Main Unit Shipping Weight (Kg) |
16.3 |
18 |
16.4 |
18.3 |
||||
Battery Module Shipping Dimensions WDH (mm) |
578*796*353 |
|||||||
Battery Module Shipping Weight (Kg) |
52 |
- |
58 |
- |
||||
Environmental Parameters |
||||||||
Operating Ambient Temperature |
0°C - 50°C |
|||||||
Operating Ambient Humidity |
0 - 95% (non-condensing) |
|||||||
Storage Temperature |
-25°C - 55°C |
|||||||
Operating Noise (Typical Load, 1m away) |
≤45dB |
≤45dB |
≤50dB |
≤50dB |
||||
Protection Level |
IP20 |
|||||||
Standards and Certifications |
||||||||
Product Standard |
IEC61000/IEC62040/GB4943/GB7260 |
|||||||
Product Certification |
TLC/Energy-saving Certification/CE |
|||||||