Model |
HP1000G(S) |
HP1500G(S) |
HP2000G(S) |
HP3000G(S) |
||||
Capacity |
10kVA |
15kVA |
20kVA |
30kVA |
||||
Main Input |
||||||||
Rated Voltage |
380Vac (Three - phase + N) |
|||||||
Voltage Range |
304Vac - 478Vac (Line voltage, full load); 304Vac - 228Vac (Line voltage, with a linear derating from 100% - 80% load) |
|||||||
Frequency Range |
40Hz - 70Hz |
|||||||
Power Factor |
≥0.99@100% load; ≥0.98@50% load |
|||||||
Current Harmonic Content |
THDi < 3% (100% linear load); THDi < 5% (100% non - linear load) |
|||||||
Inverter Output |
||||||||
Output Voltage |
380/400/415Vac |
|||||||
Voltage Accuracy |
±1% @ Balanced load; ±5% @ Unbalanced load |
|||||||
Total Harmonic Distortion (THD) |
THDu≤2% (100% linear load); THDu≤4% (non - linear load) |
|||||||
Power Factor |
1 |
0.9 |
||||||
Frequency Range (Synchronous Range) |
Default ±2Hz; ±0.5Hz, ±1Hz, ±3Hz (Adjustable) |
|||||||
Frequency Range (Battery Mode) |
50Hz ± 0.1Hz or 60Hz ± 0.1Hz |
|||||||
Overload Capacity |
< 105%, long - term; < 110%, 60 minutes; 110 - 125% rated load, 10 minutes; 125 - 150% rated load, 1 minute; > 150%, 200ms |
|||||||
Current Peak Ratio |
3:1 |
|||||||
Transfer Time |
||||||||
Utility ↔ Battery |
0 ms |
|||||||
Inverter ↔ Bypass |
0 ms |
|||||||
Inverter ↔ ECO |
< 2 ms |
|||||||
Efficiency |
||||||||
Inverter Mode |
≥95% |
|||||||
ECO Mode |
≥99% |
|||||||
Battery |
||||||||
Battery Model |
Varies according to application |
|||||||
Battery Quantity |
Default 32 sections; 30 - 44 (±15 - ±22 sections) (Adjustable) |
|||||||
Charging Current |
Capacity × 15%/N/12 (N = ±15 - 22) |
|||||||
Charging Voltage |
±13.65Vdc × N ± 1% (N = ±15 - 22) |
|||||||
Physical Characteristics |
||||||||
Dimensions Depth x Width x Height (mm) |
685 x 280 x 725 |
|||||||
Net Weight (kg) |
49 |
50 |
51 |
52 |
||||
Environmental Conditions |
||||||||
Operating Temperature |
0 - 40°C (Battery life will be shortened in an environment above 25°C) |
|||||||
Relative Humidity |
0 - 95% non - condensing |
|||||||
Altitude |
No derating within 1000m, 1% derating per 100m increase above 1000m |
|||||||
Noise Level |
≤60dB(A) @ 1m |
|||||||
Management |
||||||||
Intelligent RS - 232/RS - 485 |
Support Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC |
|||||||
Optional SNMP |
Support power management by SNMP manager and web browser |
|||||||